UC-NRLF 5DM ~: - ' . , ;v: :./ , 'V:~. "; : , ' i . ~3i BLAW-KNOX TRANSMISSION POLE (Patents Applied For) FOMM NO 941 TRANSMISSION TOWERS Being a reprint of a paper read by E. L. Gemmill, Chief Engi- neer of the Transmission Tower Department of Blaw-Knox Company, Pittsburgh, before the Engineering Society of the same company. To which have been added many tables of properties of wires, sags, loads and curves, formulae, etc., to make it a most complete reference book for all interested in the subject. BLAW-KNOX COMPANY GENERAL OFFICES: PITTSBURGH, PA. DISTRICT OFFICES NEW YORK CHICAGO SAN FRANCISCO 165 Broadway Peoples Gas Bldg. Monadnock Bldg. BOSTON DETROIT Little Bldg. Lincoln Bldg. Catalog No. 20 Copyright 1920, Blaw-Knox Company Fig. A Double Circuit Tower, for 110,000 Volt Line TRANSMISSION LINE TOWERS It is only within the last twenty-five to thirty years that it has been considered advisable to carry overhead electric power transmission lines on anything else than wood poles. But with the ever increasing tendency to concentrate power house units, and consequently to make fewer and larger installations, spaced farther apart, it has become necessary to transmit electrical energy over greater distances. This, in turn, has made it advisable to set a higher limit for the voltage at which the electrical energy will be conveyed from one point to another, in order to reduce to the lowest possible minimum the loss in transmis- sion. The using of these higher voltages has, of course, brought in its train the necessity of making more careful provisions for supporting the conductors by means of which the electrical energy is transmitted from one point to another. Naturally, the first change made in the general scheme in vogue was to place the conductors farther apart, which necessitated the use of better cross arms for supporting them. At the same time it was also imperative that, with increased voltage, more clearance be allowed between the ground and the lowest conduc- tor wires under the worst possible conditions of operation. This could best be accomplished by making the supporting structures higher. So long as the wires were kept only a short distance above the ground, the wood poles made an ideal support for them under ordinary conditions; but when higher supports had to be considered, transmis- sion line engineers began looking about for other supporting structures which would lend themselves more readily to all the varying condi- tions of service. The steel structure was immediately suggested as the proper support to take the place of the wood poles, and many arguments were ad- vanced in its favor. But these supports when built of steel were more expensive than the wood poles had been, and in order to keep the total cost of the line equipment down to a minimum, and to make such an installation com- pare favorably with a similar line using the wood poles, it became necessary to space the steel supports farther apart, so as to use fewer of them to cover the same length of line. 4fl44<)9 4 Transmission Towers The steel support, however, had come to stay, and the whole prob- lem resolved itself into a matter of making a careful investigation and study of each installation, in order that there might be used that sys- tem which apparently worked out the best in each particular case. From these several projects there have been evolved the different types of structures in use today for transmission line work. They may be roughly divided into three general types, namely: Poles Flexible Frames Rigid Towers POLES All supports that are relatively small at the base or ground line are generally classified as Poles. In plan at both ground line and near the top they are made in several different shapes. They may be round, square, rectangular, triangular, or of almost any other section. As a rule, their general outline is continued below the ground line to the extreme bottom of the anchorage. They are usually intended merely to take care of the vertical loads combined with horizontal loads across or at right angles to the direction of the line. They may have greater strength transverse to the line than in the direction of the line, but they are often made of the same strength in each direction. Poles are very rarely designed to take care of any load in the direction of the line when combined with the specified load across the line. They must be spaced closer together than the heavier structures but can be spaced much farther apart than wood poles. A very common spacing for steel poles is about 300 feet apart. FLEXIBLE FRAMES Flexible Frames are heavier structures than the poles, and are intended to take care of longer spans. Like the poles, their chief func- tion is to take care primarily of transverse loads with a small margin of safety so that under unusual conditions of service they could also pro- vide a little resistance in the direction of the line; i. e., in a measure, distribute a load coming in this direction over a number of supporting structures, and transfer such a load to the still heavier structures placed at regular intervals in the line. Or the flexible frames may transfer all loads coming on them in the direction of the line to a point where they will be resisted, by a frame of similar construction and Transmission Towers 5 strength, but which is made secure against the action of such loads by being anchored in this direction with guy lines. These flexible frames are almost always rectangular in plan. Gener- ally, the parallel faces in both directions will get smaller as the top is approached, but often the two faces parallel to the direction of the line will be of the same width from the bottom to the top. But the two faces transverse to the line almost always taper from the ground line up, and get smaller toward the top. The two faces parallel to the line are generally extended below the ground line to form the anchorages. RIGID TOWERS Rigid Towers are the largest and heaviest structures made for transmission line supports, and, as would be implied by the designa- tion given them, they are intended to have strength to carry loads coming upon them, either in the direction of the line or at right angles to this direction. They are usually designed to take a combination of loads in both directions. These towers are built in triangular, rec- tangular, and square types, depending upon the particular conditions under which the structure is to be used. When a plan of the tower at the ground line is square in outline, each side of the square will be very much larger than in the case of either poles or flexible frames. The width of one side of a rigid tower, measured at the ground line, will vary somewhere between about one-seventh and one-third of the total height of the structure. This dimension is usually determined by the construction which will give the most economical design, especially when there are a large number of the towers required; but it often happens that the outline of one or more of the structures will be deter- mined by local conditions which are entirely foreign to the matter of economy of design. Then, too, the conditions of loading may be such as to make a special outline the most economical design. LOADINGS There are three kinds of loads which come upon transmission line supports: (1) The dead load of the wires together with any coating on them; also the dead weight of the structure itself. (2) Wind loads on the wires and the structure transverse to the direction of the line. 6 Transmission Towers (3) Pulls in the direction of the line caused by the dead load and the wind load on the wires. The dead load on the wires consists of the weight of the wire itself, plus the weight of any insulating covering, plus the weight of any coat- ing of snow or sleet. In most installations the conductors are not covered with any insulating material, and hence at the higher tempera- tures the dead load will be the weight of the wire only. At the lower temperatures the wires may be coated with a layer of ice, varying up to a thickness of 1 " or more, all around the wire. In some instances ice has been known to accumulate on conductor wires until the thick- ness of the layer would be as much as 1}^" a ll around the wire. But such instances are very rare, especially on wires carrying high voltages because there is generally enough heat in these wires to interfere with the accumulation of much ice on them. But the heaviest coating of ice alone does not often produce the worst conditions of loading for the conductor and the supporting structure. The worst condition of loading is that resulting from the strongest wind blowing against a conductor covered with that coating which offers the greatest area of exposed surface to the direction of the wind under all the several con- ditions obtaining. This will almost always be true when the wind is blowing horizontally and at right angles to the direction of the line. In this case the total horizontal load on the supporting structure from the wires is the combination of the wind load against the wires and the unbalanced pull in the direction of the line, which is produced by the resultant of the horizontal wind load and the weight of the wire itself and any covering. But it does not follow that this condition will always give the maximum load on the structure. In mountainous districts it may happen that a transmission line will be subjected to a gust of wind blowing almost vertically downward, in which case this pressure, being added directly to the weight of the wire and the ice load, may lead to much more serious results than a wind of equal or even greater intensity blowing horizontally across the line. It may happen in some districts where large sleet deposits are to be encoun- tered, that the vertical load from the dead weight of the wire and its coating of ice will be so great as to produce in the wire a tension large enough to break the wire, even without any added load from the wind. This is especially true if the wire is strung with a very small sag. Since the design of the transmission line supports is determined very largely by the loads which it is assumed will come upon them, and Transmission Towers 7 since the load resulting from the pull in the direction of the line is very often the dominating factor; and, further, since this load is a function of the resultant load on the wire produced by the wind load and the dead load, it naturally follows that the assumptions made regarding the amount of this resultant loading are a matter of prime importance. For this reason some very extensive experimenting has been done to determine the amount of wind pressure against wires, either bare or covered, under extreme conditions of velocity, density of air and tem- perature. Careful observations have also been made to find out, as near as possible, what is the maximum quantity of ice that will adhere to a wire during and after a heavy storm. It not infrequently happens that the temperature falls and the wind velocity increases immediately after a sleet storm. The falling temperature, of course, tends to make the ice adhere more closely to the wires. On the other hand, a rising wind will tend to remove some of the ice from the wires. In places where the lower temperatures prevail, the wind velocity rarely gets to be as high as in the warmer districts where sleet cannot form. On the other hand, a moderate wind acting on a wire covered with a coating of ice, will oftentimes put much more stress into the wire than a higher wind acting on the bare wire. This means that the conditions of loading are altogether different for different sections of the country. It is now generally assumed that in those districts where sleet formation is to be met, the worst condition of loading on the wire will be obtained when the wires are covered with a layer of ice Yl" thick, the amount of the wind pressure on them, of course, depending upon the wind velocity and the density of the air. WIND PRESSURE ON PLANE SURFACES The wind pressure per unit area on a surface may be obtained by the following formula: V 2 W P = K in which 2 g v = velocity of wind in feet per second; W = weight of air per unit cube; g = acceleration of gravity in corresponding units; K = coefficient for the shape of the surface. v 2 W The factor is called the velocity head. 8 Transmission Towers In considering the pressure on any flat surface normal to the direc- tion of the wind, the pressure may be regarded as composed of two parts : (1) Front Pressure (2) Back Pressure The front pressure is greatest at the center of the figure, where its highest value is equal to that due to the velocity head. It decreases toward the edges. The following conclusions are generally regarded as fair and reliable deductions from the results of many experiments made by several investigators, to determine the amount and distribu- tion of wind pressures on flat surfaces : (1) The gross front pressure for a circle is about 75% of that due to the velocity head, while for a square it is about 70%, and for a rectangle whose length is very long compared with its width it is somewhere between 83% and 86%. (2) The back pressure is nearly uniform over the whole area except at the edges. (3) This back pressure is dependent on the perimeter of the surface and will vary between negative values of 40% and 100% of the velocity head. (4) The maximum total pressure on an indefinitely long rec- tangle of measurable width may be taken at 1.83 times the velocity head pressure. For a very small square, the coefficient may be as small as 1 . 1 . Using the value for W corresponding to a temperature of freezing, or 32 F., and a barometric height of 30 inches, which is 0.08071 pounds per cubic foot, and changing the wind velocity from feet per second to miles per hour, the formula for normal pressure per square foot on a flat surface of rectangular outline becomes : P _ i o, x 0-08071 5280 5280 3 X 2 x 32.2 X 60760 X 60^60 X V or P = 0.0049335 V 2 WIND PRESSURE ON WIRES In the case of cylindrical wires the pressure per square foot of pro- jected area is less than on flat surfaces. The coefficient by which the pressure on flat surfaces must be multiplied to obtain the pressure on Transmission Towers 9 the projected surface of a smooth cylinder, varies, according to different authorities, from 45% to 79%. Almost all Engineers in this country assume this coefficient to be one-half, and, on this assumption our formula becomes P = 0.00246675 V 2 for the pressure per square foot on the projected area of the wire, with any coating it may have on it. Mr. H. W. Buck has given the results of a series of wind pressure experiments made at Niagara on a 950 ft. span of .58 inch stranded cable, erected so as to be normal to the usual wind. From the data obtained, the following formula was derived: P = 0.0025 V 2 in which P = Pressure in pounds per sq. ft. of projected area V = Wind velocity in miles per hour. For solid wire previous experimenters had derived the formula P = 0.002 V 2 It is to be noted that Mr. Buck's formula gives values for pressures 25% in excess of the other formulas, which might be attributed to the fact that for a given diameter, a cable made up of several strands, pre- t sents for wind pressure a different kind of surface than a single wire. If we could be sure that this difference exists, then it would be well worth while to take this into consideration when determining the loads for which a tower is to be designed, and to make a careful distinction between towers which are to support solid wires and those which are to carry stranded cables. Almost all Engineers are inclined to accept the formula given by Mr. Buck, and to assume it to be correct for both types of conductors. The fact that this formula agrees so closely with the formula arrived at by assuming that the pressure on the projected area of a cylindrical surface is 50% of the pressure on a rectangular flat surface, would seem to warrant accepting it as being correct. WIND VELOCITY In assuming the loadings for which a line of towers are to be designed, the first thing to be determined is the probable wind velocity which will be encountered under the worst conditions. Our calculations, of course, should be based on actual velocities. This is mentioned be- cause it is necessary to distinguish between indicated and true wind 10 Transmission Towers velocities. The indicated velocities are those determined by the United States Weather Bureau. Their observations are made with the cup anemometer and are taken over five minute intervals. The wind velocities over these short periods of time are calculated on the assumption that the velocity of the cups is one-third of the true velo- city of the wind, for both great and small velocities alike. As the result of considerable investigation, it has been found that this assumption is not correct, but that the indicated velocity must be corrected by a logarithmic factor, to convert it into the true velocity. The actual wind velocities corresponding to definite indicated velocities, as given by the United States Weather Reports, are as follows : Indicated Actual Indicated Actual 10 9.6 60 48.0 20 17.8 70 55.2 30 25.7 . 80 62.2 40 33.3 90 69.2 50 40.8 100 76.2 It is generally conceded that the wind pressure increases with the height above the ground, and that it is more severe in exposed posi- tions, and where the line runs through wide stretches of open country, than it is in places which are more or less protected by their sur- roundings. If we accept the theory advanced by some, to the effect that the ground surface offers a resistance to the wind, which materially lessens its force, then we must conclude that after a certain altitude has been reached the effect of this resistance becomes negligible, and that beyond that altitude the rate of increase in wind pressure must be small. This is especially true, because the density of the air is less in the higher altitudes, which tends to counteract some of the effect of increases in velocity. But experimental data bearing on this matter are very limited, so that the rate of increase in wind pressures for higher elevations above the ground, must in each case be determined by the judgment of the Engineer who is designing the installation. The curve on Fig. 1 shows the relationship between Indicated velocity and Actual velocity, and the curve on Fig., 2 shows the pres- sure in pounds per square foot of projected area of wire, corresponding to actual velocities in miles per hour. By placing above the curve given on Fig. 2 a similar curve corresponding to the indicated velocities, a direct comparison between the two different velocities may be made in terms of pressure. This is shown in Fig. 3. Transmission Towers 11 For the general run of transmission line work no special allowance is made for the pressures on towers at different elevations; but pressures are used which are considered to be fair average values for the par- ticular location of the line and for towers of heights which usually prevail. But, of course, there is a distinction made between require- ments for a low pole line and for a line on high steel towers. This applies both to the wind pressures, which it is assumed will be en- countered, and also to the factor of safety expected in the construction throughout. ou 7D J A fin V .. t- - 1- [ J y^ r f . f - - ? k 5 ( A | VELOCITY, $ i ^ _ :f .... ... I .. j- - ACTUAL I i .-.L. - -f 'i ~~~~ \ f WN OF w ACTUAL i OJ j /ND/ GATED * in WIND VELOCITIES . .7- - m - 2 - - -- Ju I - ir I 1 \ I *i ^ fin At 7 K 9 fit i a 9 IOL h'll j in ?n INDICATED VELOCITY; miles per hour. Fig. 1 12 Transmission Towers Transmission Towers 13 14 Transmission Towers STANDARD PRACTICE FOR WIND AND ICE LOADS The Committee on Overhead Line Construction, appointed by the National Electric Light Association of New York, assumes an ice coating %* thick all around the wire, for all sizes of conductors, and maximum wind velocities of 50 to 60 miles per hour, as being an aver- age maximum condition of loading. This Committee states that 62 miles per hour is a velocity not likely to be exceeded during the cold months. Three classes of loading are considered by the Joint Committee on Overhead Crossings, as follows: Class of Loading: Vertical Component of Load on Wire: Horizontal Component of Load on Wire, or Wind Load Across Line: A B C Dead Dead + Y 2 " Ice Dead + M" Ice 15 Lbs. per Sq. Ft. 8 Lbs. per Sq. Ft. 11 Lbs. per Sq. Ft. For the Class "B" Loading the ordinary range of temperature is given as 20 to 120 F. For the calculation of pressures on supporting structures the require- ments are 13 Ibs. per sq. ft. on the projected area of closed or solid structures, or on V/% times the projected area of latticed structures The same Joint Committee allows a maximum working stress on cop- per of 50% of the ultimate breaking stress; in other words, the wires may be stressed to a point very near to the elastic limit. An analysis of these three classes of loadings would seem to suggest that Class "A" be used for lines in the extreme Southern part of the United States, and that Class "B" be used for all other lines in this country, unless it be for a few lines which might be located in regions where especially cold weather is to be encountered, along with very severe wind storms. For such lines Class "C" would certainly be ample to take care of the most extreme conditions. Interpreting these loadings in terms of wind velocities, class "A" would allow for an indicated wind velocity of 101.8 miles per hour, or an actual velocity of 77.46 miles per hour, acting against the bare con- ductor. Class "B" provides for an indicated wind velocity of 71.96 miles per hour, or an actual velocity of 56.57 miles per hour, applied Transmission Towers 15 to the projected area of the wire covered with a layer of ice yy thick all around. Class "C" assumes an indicated velocity of 85.9 miles per hour, or an actual velocity of 66.33 miles per hour, against the wire covered all around with a layer of ice %" thick. It has been contended by some Engineers that sleet does not deposit readily on aluminum, owing to the greasy character of the oxide which forms on the surface of aluminum conductors, and that because of this fact the wind loads acting on such lines should not be taken so high as when copper wires are used. But the experience and observation of many other Engineers does not confirm this assumption. CURVES ASSUMED BY WIRES When the wires are strung from one structure to another throughout the line, they assume definite curves between each two of the struc- tures, these several curves, of course, depending upon the different conditions attending the stringing. If a heavy uniform string which is considered to be perfectly flexible, is suspended from two given points, A and B, and is in equilibrium in a vertical plane, the curve in which it hangs will be found to be the common catenary. This is shown in Fig. 4. Tension, T, CATENARY At i X *[ DlRKTIHX-1 I 1 ON-X N Fig. 4 16 Transmission Towers CATENARY Let D be the lowest point of the catenary, i. e., the point at which the tangent is horizontal. Take a horizontal straight line O X as the X axis, whose distance from D we may afterwards choose at pleasure. Draw D O perpendicular to this line, and let O be the origin of co- ordinates. Let be the angle the tangent at any point P makes with O X. Let To and T be the tensions at D and P respectively, and let the arc D P = Z. The length D P of the string is in equilibrium under three forces, viz: the tensions T and T, acting at D and P in the directions of the arrows, and its weight w Z acting at the center of gravity G of the arc D P. Resolving horizontally we have T cos e = To (1) Resolving vertically we have T sin = w Z (2) Dividing equation (2) by equation (1) dy w Z dx " To (3) If the string is uniform w is constant, and it is then convenient to write : To = w C. To find the curve we must integrate the differential equation (3). We have, z dz /. dy = /. y + A = db We must take the upper sign, for it is clear from (3) that, when x and Z increase, y must also increase. When Z = O, y + A = C. Hence, if the axis of X is chosen to be at a distance C below the lowest point D of the string, we shall have A = O. The equation now takes the form, y 2 = Z 2 + C 2 (4) Transmission Towers 17 Substituting this value of y in (3), we find, Cdz V Z 2 -f C 2 = dx ' where the radical is to have the positive sign. Integrating, C log (z + VZ 2 + C 2 ) = x -f B But x and Z vanish together, hence B = C log C. From this equation we find, v z 2 + c 2 + z = c e c Inverting this and rationalizing the denominator in the usual manner, we have V Z 2 + C 2 Z = CC~' Adding and subtracting, we deduce by (4) The first of these is the Cartesian equation of the common catenary. The straight lines which have here been taken as the axes of X and Y are called, respectively, the directrix and the axis of the catenary. The point D is called the vertex. Adding the squares of (1) and (2), we have by help of (4), T 2 = w 2 (Z 2 + C 2 ) = w 2 y 2 ; /. T = w y (6) The equations (1) and (2) give us two important properties of the curve, viz: (1) the horizontal tension at every point of the curve is the same and equal to w C; (2) the vertical tension at any point P is equal to w Z, where Z is the arc measured from the lowest point. To these we join a third result embodied in (6), viz: (3) the resultant tension at any point is equal to w y, where y is the ordinate measured from the directrix. Referring to Fig. 4, let PN be the ordinate of P, then T = w PN. Draw NL perpendicular to the tangent at P, then the angle P N L = Hence, PL = PN sin = Z by (2) N L = PN cos o = C by (1) 18 Transmission Towers These two geometrical properties of the curve may also be deduced from its cartesian equation (5). By differentiating (3) we find, 1 do 1 dz C 1 " /"** I 1 /i cos 2 # dz C do cos 2 (7) v 2 f> is also = =; We easily deduce from the right-angled triangle P N H, that the length of the normal, viz: PH, between the curve and the directrix, is equal to the radius of curvature, viz., p, at P. At the lowest point of C 2 the curve D, the radius of curvature, /, = = C. It will be noticed that these equations contain only one undetermined constant, viz., C; and when this is given, the form of the curve is absolutely determined. Its position in space depends on the positions of the straight lines called its directrix and axis. This constant C is called the parameter of the catenary. Two arcs of catenaries which have their parameters equal are said to be arcs of equal catenaries. Since /> cos 2 = C, it is clear that C is large or small according as the curve is flat or much curved near its vertex. Thus, if the string is suspended from two points A and B in the same horizontal line, then C is very large or very small compared with the distance between A and B, according as the string is tight or loose. The relationship between the quantities y, Z, C, />, and and T in the common catenary may be easily remembered by referring to the rectilineal figure P L N H. We have PN = y, PL = Z, NL = C, PH = />, T = w- PN and the angles LNP, NPH are each equal to 0. Thus the important relations (1), (2), (3), (4) and (7) follow from the ordinary properties of a right-angled triangle. The co-ordinates of the center of curvature for the catenary are: a (abscissa) = x Vy 2 C 2 ft (ordinate) = 2y When two or more unequal catenaries have similar outlines so that *~^ the ratio ^ is the same for all of them, the curvature between the x points D and P will also be the same for all these catenaries. From Transmission Towers 19 this it follows that, at similar points on the different catenaries, the several radii of curvature will vary directly as the values of x for the different curves. The radius of curvature at the lowest point D has already been shown to be equal to C, the parameter of the catenary. Since C and y C both vary directly as the value of x for these unequal but similar catenaries, it is evident that y must also vary in the same manner. It will be seen from the triangle PLN, that when C and y both vary in the same manner, LP or Z, which is the length of the arc DP, must also vary in the same manner. ELASTIC CATENARY When a heavy elastic string is suspended from two fixed points and is in equilibrium in a vertical plane, its equation may be found as follows : Using the same figure as for the inelastic string and denoting the unstretched length of arc D P by Zi, let us consider the equilibrium of the finite part D P; Tcosfl = To (1) . dy _ _ wzi .. Zi , , (2) ' dx To " C From these equations we may deduce expressions for x and y in terms of some subsidiary variable. Since Zi = C tan by (3), it will be convenient to choose either Zi or as this new variable. Adding the squares of (1) and (2), we have, -P = W 2 ( C + Z! 2 ) (4) Since = cos and -p = sin 0, dz dz we have by (1) and (2) IT * - -T where the constants of integration have been chosen to make CV x = O and y = C + -^- at the lowest point of the elastic catenary. The axis of X is then the statical directrix. 20 Transmission Towers We have the following geometrical properties of the elastic catenary : (2) (3) All of these reduce to known properties of the common catenary when E is made infinite. These equations have value only from an academic viewpoint. They are too unwieldy to be of any practical value in determining the properties of curves, assumed by transmission line wires under different working conditions. These equations would be still further compli- cated, if we attempted to make them take care of changes resulting from conditions of loading due to different temperatures. PARABOLA If we consider the weight of the wire to be uniformly distributed over its horizontal projection, instead of along its length, its equation will be found to be that of a parabola. PARABOLA Fig. 5 Transmission Towers 21 By referring to Figure 5 ^nd considering the equilibrium of any part OP of the wire, beginning at the lowest point O, the forces acting on this part are seen to be the horizontal tension H at O, the tension T along the tangent at P, and the total weight W of the wire, OP. As this weight is assumed to be uniformly distributed over the horizontal projection OP 1 = x of OP, the weight is W = w x, and bisects OP 1 . Resolving the forces in the horizontal and vertical directions, we find as conditions of equilibrium, H + T ^ = O, wx + T ^ = O, dz dz whence, eliminating dz, -p- =77 x - Integrating and considering that x = O when y = O, we get w 2 H y = 777 x 2 , which may be put in the form x 2 = y. This is the 2 ri w ' equation to a parabola. If we substitute - for x, and S for y, in the equation for the curve, //y 2H \2/ w it becomes ( - ) = S or w / 2 = 8 HS, w/ 2 from which H = -r^-, 00 which is the well known equation for determining the horizontal ten- sion in the wires, when the two points of support are in the same hori- zontal plane. In that case - equals one-half of the span, and S equals the sag or deflection of the wire below the plane of the supports. The three forces H, T, and W, are in equilibrium; they must inter- sect in a point R which bisects OP 1 , and the force polygon must be similar to the triangle RPP 1 . Drawing such a force diagram K L M, and making L M equal to W or w x, and MK equal to H, KL will be the value of T and equal to A/H 2 + (w x) 2 . Substituting for H and x their values in terms of w, / and S, this // W/2 Y,/ 1 Y /w 2 / 4 becomes ^(- ) + (wjj = ^- + law 2 / 22 w / ^- = - / 2 + 16S 2 . 22 Transmission Towers A quantity \/A 2 + a 2 , when a is very small relatively to A, may be a 2 approximated by using A -f -r-r ; hence, an approximation for the above value of T is, w/ 2 w / / 7 . 16 S 2 \ w / 2 c 8sV / + ^rj' or '^s + wS - In this form it is very similar to the expression for the tension in the wire at the insulator supports, derived by assuming the curve to be a catenary. It will readily be seen from the above that for very small sags in short spans the maximum tension at the insulator supports is very little more than the tension at the middle of the span. But it must be noted that in order that the above assumption may be warranted, it is essential that the span considered, be short, and that the length of wire be little more than the span. This, of course, means that the sag in the wire must be rather small. ? 14" The equation for the parabola x 2 = y has, for the coefficient of y, a constant which is equal to four times the distance between the directrix of the parabola and the vertex O, as shown in Fig. 6. Fig. 6 Transmission Towers 23 The directrix is shown passing through the point A, and is parallel to the X axis. The line OY is the axis of the curve. If a line is drawn tan- gent to the curve at any point P, this tangent will intersect the Y axis at a point B, such that the distance BO will equal the distance OC, where C is the point of intersection of the Y axis with a line drawn through the point P, parallel to the X axis. The length BC is the subtangent and is equal to twice the ordinate of the point of contact. The line PD drawn through the point P and perpendicular to the tangent BP, will intersect the Y axis at point D. The length CD is the subnormal of the curve, and is constant for all points on the curve. It is equal to one-half the co-efficient of y in the original equation, and is therefore TT equal to . The angles TRX and ORB are each equal to the angle AV PDC or e. Tan# = R P PARABOLIC ARC WITH SUPPORTS AT DIFFERENT ELEVATIONS The curve in which a suspended wire hangs, may be considered to extend indefinitely in both directions, and the suspended wire may be secured to rigid supports at any two points, such as N and U, lying on this curve (Fig. 7), without altering the tension in the wire. The law of this parabola is PARABOLA : 2 = Ky, SPAN SUPPORTS AT DIFFERENT LEVELS U Span measured horizontally = ^^ i i "^ 1 y A 24 Transmission Towers and in the case of a suspended wire the multiplier K is directly propor- tional to the tension H, and inversely proportional to the density of the conductor material. The value of K in terms of the horizontal tension and the weight of the conductor has already been found to u 2H be - . w Let S = sag below level of lower support, B = horizontal distance of lowest point of wire from lower support, h = difference in level of the two supports, / = length of span measured horizontally, all as indicated on Fig. 7; then, by inserting the required values in equation x 2 = Ky, the following equations are derived therefrom: B 2 = K S, (/ B) 2 = K (S + h), or, / 2 2/B + B 2 = KS + Kh, from which B 2 on one side and its equivalent KS on the other side can- cel out, leaving I 2 2/B = Kh. Therefore, Kh , B 2 2 ' K From an inspection of the formula B = - , , it is seen that if 2> I Kh = / 2 , the lowest point of the wire coincides with the lower support N, while if Kh is greater than / 2 , the distance B is negative, and there may be a resultant upward pull on the lower insulator N a point to bear in mind when considering an abrupt change in the grade of a transmission line. We may consider the curve of the wire between the two supports N and U as being made up of two distinct parts, NO and OU. The part NO will be equivalent to one-half of a curve whose half span measured horizontally is B, and whose sag is S. Similarly, the part OU will be equivalent to one-half of a curve whose half span measured hori- zontally is / B, and whose sag is S -)- h. It is possible, and sometimes convenient, to express the formulas for wires suspended from supports not at the same level, in terms of the equivalent sag (Se) of the same wire, subjected to the same horizontal tension when the horizontal span (/) is unaltered, but the supports are on the same level. Transmission Towers 25 For such a condition, the equation to the curve becomes from which ^ = 45; If we substitute for K in the above formulas, its equivalent value K = , then we get the following set of formulas, in which B, S, /, and h, are all as indicated in Fig. 7. COMPARISON OF CATENARY AND PARABOLA If a straight line is drawn through the point P and any other point K on the parabola, shown in Fig. 6, and this chord KP is bisected at the point M, a line drawn through this point M and parallel to the Y axis will bisect all other chords which are parallel to the chord KP. From this it follows that a line SU drawn tangent to the parabola and parallel to the chord KP, will be tangent to the curve at a point L which lies on a line that is drawn parallel to the Y axis and through the point M. Another property of the parabola is, that the tangents to the curve at the points K and P will intersect at the point N, which also lies on the line that passes through the points L and M. If the horizontal projection of the chord KP be designated by /, then the horizontal projection of KM, MP, KN, and NP will each be equal to 1 AL The total tension T in the wire at any point on the curve equals + (wx) 2 , or, T,.ygy + - But it is seen from the figure that V(!7 + x 2 = DP, /. T = w DP . 26 Transmission Towers In the case of the catenary the total tension in the wire is T = w y in which y = VC 2 + Z 2 But, when we compare a catenary and a parabola having equivalent TT horizontal tensions. C = .it will be seen that the two formulas for w total tension in the wire differ only in that the value Z, which is the true length of the arc, is used in the one case, -where x, which is the horizontal projection of the length, is used in the other. But T will always be greater for the catenary except at the lowest point of the curve. The radius of curvature of the parabola 2H ^ x 2 = y is p = w w ' c . SmV in which y is the angle which the tangent to the curve makes with the Y axis. TT /> sin 3 sin 2 y = DP from which DP ^ DZ. sn

cos 3 9 In the case of the catenary, cos 2 o A comparison of these two, shows that the radius of curvature for the parabola, at a point where the tangent makes an angle with the horizontal, is times that for a similar point on the catenary. Transmission Towers 27 At the lowest point of the curve the radius of curvature is the same for both the parabola and the catenary, when the horizontal tension is the same. It is also true that, when the horizontal tension at the lowest point of the parabola is equivalent to that at the lowest point of the catenary for the same span and loading conditions, the sag at this point below the plane of the supports will be very nearly the same for the two curves. But the outlines of the two curves differ at all points between the lowest point and the point of support. This difference between the outlines of the two curves becomes greater as the spans and the sags are made larger. It is because of this difference in the outlines of the two curves that the sags will be nearly equal for only one loading con- dition. Any change in the loading condition will produce different changes in the lengths of the two curves, and hence, will make the sags different. REACTIONS FOR SPANS ON INCLINES When wires are strung on towers that are located on steep grades, it is very necessary that we determine carefully the reactions at the points of support and also the deflection of the wire away from a straight line joining the two points of support for any given span. This case is shown in Fig. 8. PARABOLA Fig. 8 28 Transmission Towers If we have given the horizontal distance, /, between the supports A and B and also the vertical distance, h, that B is above A, together with the maximum tension, T, in the wire at the point of support B, we can determine the reactions at both of the supports and also the sag in the wire. The wire ADRB is in equilibrium under three forces; viz., the ten- sions acting at A and B in the directions of the tangents, and its weight w/ 1 acting at its center of gravity. These three forces intersect at the point Z, and the vertical line through this point passes also through the point C on the line AB and midway between A and B. On this vertical line lay off the distance OU equal to W or w/ 1 , and let it be bisected at the point C so that OC equals CU or J/ w/ 1 . Complete the force diagram by drawing UV and OV parallel respectively to ZB and AZ. UV will then be the tension in the wire at the point B, and OV will be the tension at the point A. The vertical component of the re- action at B is the vertical component of UV and is equal to UM. The vertical component of the reaction at A is the vertical component of OV and is equal to MO or UO UM. Complete the parallelogram of forces by drawing OF parallel to UV and FU parallel to OV. The points F and V must lie on the line AB. Let the tension UV in the wire at the point B be denoted by T. Let be the angle made by the line AB with the horizontal line AX, and let be the angle between the lines FO and AB. Let ,3 be the angle which the tangent at the point B makes with the horizontal plane. Angle O C F = ft + 90. Sin

an having supports at unequal heights above a given horizontal plane, if the horizontal distance from the higher support to the lowest point of the wire is known, the stress and sag in this part of the span can be determined by considering this part as one-half of a span equal to twice this distance. The smaller stress in the other part can be determined in the same manner. The following formulas, based upon the catenary, give the horizontal distance from the higher support to the lowest point of the wire, . I , hT h_ (A) 1>U -h + V~d (B) where, / = the span in feet. / u = the horizontal distance in feet from the higher support to the lowest point of the wire, h = the difference in height of the two supports in feet. T = the stress in pounds in the wire at the higher support, with one pound per foot load on the conductor, d = the sag in feet measured from the higher point of support. Formula (A) is useful when the span and the stress to be allowed in the wire are given, and formula (B) when the span and the sag are given. These formulas are approximate in that the horizontal projection of the wire is substituted for the actual length of it. Formula (A) is correct within from 2% to 4%, when neither sag nor difference in heights of supports exceeds 15% of the span. Formula (B) has an error of less than 1% under these conditions. SPACING OF TOWERS The problem of determining the type and the spacing of the towers to be used, is one that requires considerable study of all the foregoing, as the towers are only a part of the complete installation, and a saving on one item may easily be more than offset by an increased cost of 38 Transmission Towers some other items affected by the same conditions which made the initial saving. In other words, it is a case of balancing one condition against another, to determine what is the best possible combination. The supporting structures must, of course, be placed as far apart as possible; but an analysis of the various sag conditions for the wires makes it evident that there are definite limits to be observed. SPACING OF CONDUCTORS After the spacing of towers has been determined, together with the size of wires to be used and the voltage to be carried by them, the next thing to consider is the spacing of the several wires and the minimum clearance from the ground line to the lowest wire under the worst loading condition. The maximum sag to be allowed must then be determined, and this condition, along with the assumed loading across the line, will determine the pull which may occur in the direction of the line on the wire. The spacing of the wires in both horizontal and vertical directions is dependent upon the voltage carried and upon the length of spans. The minimum spacing, especially in the horizontal direction, will obtain when the wires are supported on pin insulators, or are attached to the cross arms by means of strain insulators. For this condition, it is recommended that, for conductors carrying alter- nating current, the minimum separation of these conductors, at the points of support, shall be one inch for every twenty feet of span, and one inch additional for each foot of normal sag, but in no case shall the separation be less than : Line Voltage Clearance Not exceeding 6600 volts .. . 14J/2 inches Exceeding 6600 volts but not exceeding 14000 volts, 24 inches 14000 " " " " 27000 " 30 27000 " " " 35000 " 36 35000 " " " 47000 " 45 47000 " " " 70000 " 60 For voltages higher than 70000 the minimum separation should be 60 inches plus 0.6 inch for every additional 1000 volts. Transmission Towers 39 When conductors are supported by suspension insulators, the separa- tion of them horizontally must be made greater than when they are supported on pin type insulators. The amount of this increase is empirical, and is more or less a matter of judgment on the part of the Engineer who designs the line. When the conductor wire is supported from the cross arm by strain insulators, it is frequently assumed that the jumper wire will swing to a position, making an angle of thirty degrees with the vertical. It is usually assumed that the maximum swing of a suspension insulator string will be to an angle of forty-five degrees, but this depends upon the size and weight of the conductor, and also upon the assumed maximum loading. It is possible that under unusually severe conditions, two wires suspended from the same cross arm may swing toward each other until each of them will make an angle of about thirty degrees with the vertical. Or even though they do not both swing the same amount, it is a safe assumption that twice the horizontal projection of the length of one insulator string when swung to thirty degrees from the vertical, will be equivalent to the sum of the horizontal projections of the two wires when swinging toward each other under the worst conditions of service. This means that when wires are supported by suspension insulators instead of on pin type insulators, the horizontal separation should be increased by the length of one insulator string. It is generally recommended that the minimum clearance in any direction between the conductors and the tower, shall not be less than : Line Voltage Clearance Not exceeding 14000 volts 9 inches Exceeding 14000 but not exceeding 27000 15 " 27000 " " 35000 18 " 35000 " " 47000 21 " 47000 " V 7000 ....24 " Usually the suspension insulators are made sufficiently long so that when swung out to the assumed position of maximum swing, the ver- tical distance between the conductor and its supporting cross arm, or any other part of the tower, will meet all the requirements for clearance. The overhead ground wire, or wires, should be, in general, not more than forty-five degrees from the vertical through the adjoin- ing conductor. 40 Transmission Towers The several wires must be spaced far enough apart vertically so that under the worst conditions the wires will not come so close together as to make trouble electrically. This must have careful consideration, especially on the very long spans, because it is entirely possible during storms for the lowest wires to be free from ice loading or to be suddenly relieved of such loading, when they might swing up, close to the wires directly above them, which might be heavily loaded with ice and hence have considerable sag. The arrangement and spacing of the wires almost always fixes, with- in certain limits, the general type of the supporting structure to be used. This is at least true of the upper part of it. The outline of the structure below the lowest cross arm will be made that which is the most economical, unless such an outline is prohibitive on account of right-of-way or other limiting conditions. Where the transmission line consists of three conductor wires, with or without a ground wire, it very often works out to very good advan- tage to put the three conductor wires in the same horizontal plane, which means that the middle one will pass through the tower. When suspension insulators are used with this arrangement of wires, the tower must be made wide enough to allow ample clearance from the conductor when swung to maximum position either way. But if strain insulators are used, then a much narrower jtower may be used by attaching the jumper wire to a pin on the center line of the tower. The narrower tower makes a much more economical construction. When six conductor wires, with or without ground wires, are used, three of the conductors are placed on each side of the tower. These are generally placed so that the three wires in each set are in the same vertical plane, but sometimes the middle one will be put farther from the center line of the tower than the other two wires. The design of the supporting structures from this point on, consists in determining just what loads are to be considered as coming on the structures, what unit stresses shall be used throughout, and whether a com para tirely large or small investment shall be put into them. In other words, it is a matter of first importance whether these struc- tures are to be regarded for a temporary proposition, and hence made as cheaply as possible, or whether they are to be considered as part of a permanent construction and therefore figured a little more liberally. Transmission Towers 41 TEMPORARY STRUCTURES For a temporary proposition the structures are, of course, made as light as possible and are almost always painted. They are rarely gal- vanized. In such cases the assumed loadings are kept very low, and are intended to take care of only normal conditions, on the theory that if some of the structures should be subjected to loadings of unusual intensity resulting from specially severe storms, it will be more eco- nomical to replace some of them that might be destroyed than to provide additional strength in all the supports. For the same reason the unit stresses are always run as high as possible. PERMANENT STRUCTURES On the other hand, where permanency of construction is wanted, the design is made more liberal in every way. To start with, the assumed loadings are such as will be expected to take care of more than ordinary conditions of service. They will be made sufficiently high to be in themselves an insurance against possible interruptions of service due to breakdowns caused by storms. Also, the unit stresses will be kept lower and heavier material will be specified. Generally, but not always, such structures will be required to be galvanized instead of painted, so that the structure will be in service for a longer time. THICKNESS OF MATERIAL When the material is required to be galvanized, many specifications will allow web members to be made of material only y% "thick, but will require a minimum thickness of $* or possibly %" for the main posts. Almost all specifications require a minimum thickness of material of TS* for all members when painted; but some specify that no material less than % " thick shall be used when painted ; while others demand a minimum thickness of y\r" for all material, regardless of whether it is painted or galvanized. GALVANIZE FOR PERMANENCY The history of transmission line structures proves that where per- manency of construction is desired, they should always be galvanized, not painted. At least all parts of the structure in close proximity to the conductor wires should be galvanized, irrespective of what kind of a protective coating is given to the balance of the structure. This is especially true in those cases where high voltages are used. 42 Transmission Towers SPECIFICATIONS FOR DESIGNS There is no such thing as a standard practice among Engineers today regarding the method to be pursued in preparing specifications for transmission line towers on which competitive bids are to be re- ceived. Usually for a line requiring several towers, the Engineer in charge of the installation will determine the arrangement of all the wires, the limiting dimensions for the structures, and the loadings for them; but the design of the structures will be left generally to the Manufacturer, subject, however, to those provisions of the specifica- tions which are intended to insure that the towers or poles will all be designed to have the same strength. Different Engineers seek to accomplish this result in as many different ways. Some will specify the loadings under which they expect the towers to be used, and will stipulate that the design shall provide sufficient strength to take care of these loadings with a given factor of safety; others wi'.l state unit stresses which shall be used in determining the sections in the design, to take care of the stresses resulting from the above loadings. Other Engineers will increase the desired working loads by some factor which they will introduce as a margin of safety, and will then give these in- creased loadings instead of the working loadings, and will require that the structures be designed to withstand these loadings without failure. Still other Engineers will specify that certain unit stresses shall be used in determining a design, which shall support the specified loadings with a given factor of safety; and, further, that the completed structure must support loads that are twice as large as those specified, but with- out any restriction regarding unit stresses to be employed. FACTOR OF SAFETY The term "Factor of Safety" is in reality a misnomer, and, because of this, it is not always interpreted in the same way by different men. Literally speaking, the structure which is properly designed with a factor of safety of three, should sustain without failure loads three times as great as those which are expected to be the working loads under normal conditions. But the term "Factor of Safety," as it is usually interpreted and applied, means that the unit stresses used throughout shall be one-third the ultimate strength of the material entering into the construction. In actual practice the results of such an interpretation are very disappointing. In a composite structure Transmission Towers 43 made up of a large number of different pieces, some of which are under- going compression while others are in tension, the action of this body as a whole against outside forces will differ radically from what would be expected of any one of its component parts under a similar test. This, of course, is accentuated in the case of transmission towers, because they are always made as light as possible for the work required of them, and, hence when under load, they deflect considerably from their original outlines, and this in turn produces a rearrangement and entirely different distribution of stresses. The net result of all this is, that all such structures will fail when the loading on them reaches the point where some, if not all, of the members making up the construc- tion are stressed to the elastic limit for their material. Since the elastic limit for steel in either tension or compression is about one-half its ultimate strength, it follows that the structure whose members are determined by using unit stresses equal to one-third of the ultimate strength of the material, will have a total strength only 50% in excess of that required to take care of actual working condi- tions; so that, instead of having the so-called "Factor of Safety of Three" it has an actual factor of safety of one and one-half. This fact is recognized by those who first multiply the required work- ing loads by a factor which will provide a margin of safety, and then specify that the towers shall support without failure these increased stipulated loads. It is not often that, under these conditions, the specifications will call for the employment of definite unit stresses in determining the several sections of material to be used. But in all such cases, when unit stresses are specified, it will almost always be found that those recommended are close to the elastic limit for the material. UNIT STRESSES The unit stress for a member in either tension or compression is the quotient of the total load divided by the cross sectional area of the member supporting the load. This is given in pounds per square inch. The unit stress for a member in compression is less than that for a member in tension by a quantity which is a function of the ratio between the unsupported length of the member and its least radius of gyration. Usually this unit stress is determined by a straight-line formula, such as 44 Transmission Towers S c = S C in which K Sc = the desired unit stress in compression, S = the unit stress allowed in tension, L = the unsupported length of the member in inches, R = the least radius of gyration for the member, in inches, C = a constant determined by experimental investigation. The elastic limit in tension is about 27000 pounds per square inch of net section. The straight-line formula 27000 90 =r for unit stresses R in compression, gives values which have been proven by actual tests to be approximately the elastic limit for the material. Where the so-called ' 'Factor of Safety of Three" is wanted, the unit stress generally specified for members in tension is 18000 pounds per square inch of net section, while, for unit stress for members in com- pression, the formula 18000 60 is specified. K It will be noted that these values are just two- thirds of those im- mediately preceding, and, therefore, offer a margin of safety of 50%. It is not often that unit stresses smaller than these are specified for tower work, but occasionally we find specifications which are very severe, considering the infrequency of maximum or even full loads on this type of structure. It is common practice among Engineers, when specifying that the towers shall safely support certain loads, to refrain from putting any limitations on the design, such as what relationship shall be allowed as a maximum between the length of any compression member and its least radius of gyration. On the other hand, when it is stipulated that the structures shall be figured for carrying certain loads by using given unit stresses, it is almost always also stipulated that the ratio of length of compression members to their least radius of gyration shall be limited to a certain maximum value. BOLT VALUES Bolts stressed to 24000 pounds per square inch in shear have value* comparable with the strength of members which are figured on the basis of 27000 pounds per square inch of net section in tension, or 27000 Transmission Towers 45 L - 90 =? pounds per square inch of gross section in compression. From IN. this it follows that bolts need not be stressed lower than 16000 pounds per square inch in shear to get values corresponding to those resulting from using 18000 pounds per square inch of net section in tension or 18000 60 TT pounds per square inch of gross section in compression, K. for members which are to be connected by means of these bolts. It is evident that smaller values for bolts are unwarranted. Consistent practice in designing requires that the values assumed for bolts shall bear the same ratio to their elastic limit as the ratio obtaining between the working value assumed and the elastic limit for the several mem- bers which are connected by the bolts. LOADINGS In regard to the specific loadings for which the structures shall be designed, considerable depends upon where they are to be used, as there are several factors entering into this question. The first thing that should be determined is the kind and maximum value of the vertical load to be taken care of at the end of the cross arm. If the line runs through a comparatively level country, there is no reason why there should ever be any uplift at the end of the cross arm ; but if the line runs along steep grades, then there may be times when the vertical load will be upward rather than downward. This is of considerable consequence in the designing of the tower. The vertical load at the end of the cross arm is usually supported by members which run from the end of the cross arm to the main post angles at some point above the cross arm. If the vertical load is downward, these supporting members will act in tension, but if the load can ever be upward instead of downward, then, such members must be capable of taking stress in compression. In cases where the cross arms are long, which is almost always true when suspension insulators are used, these members must be made much heavier to take the stress in com- pression, rather than tension. ANGLE TOWERS The next thing to determine, if possible, is, how many towers will have to take care of angles in the line, and what will be the maximum angle encountered. If this angle should be very large, it will be neces- 46 Transmission Towers sary to provide special structures for such points in the line; but if the angle is very small, provision for it may be made by using one of the straight line towers at this point and shortening the span on each side of it. This shortening of the span reduces the wind load on the wires transverse to the direction of the line, and at the same time reduces the pull in the wires in the direction of the line, if the sag is made a greater percentage of the shortened span than it is in the case of the adjoining spans. In Fig. 11 there is shown a graphical diagram of the components of the tension in the wire, parallel to the faces of the tower, when its axis parallel to the cross arm bisects the given angle in the line. It will be seen that when the wires leading off in both directions from the end of the cross arm have equal stresses, the component "Y" in one wire balances the corresponding component from the other wire, but that the component "X" is twice what it is when only one wire leads off from the cross arm. This means that in the one case, marked condi- tion "B," the load on the tower is twice the component "X" from one wire, but that for condition "A," the load on the tower is the sum of the components "Y" and "X" from one wire. It will be noted that for condition "B" the total load on the tower from the pull in the direction of the line will just equal this pull when the tower bisects an angle of sixty degrees in the line, and that this load increases to double the pull on one wire, as a maximum limit, when the angle in the line reaches one hundred eighty degrees. For condition "A" the total load will always be greater than the pull in the wire, no matter how small the angle in the line, and the worst loading will occur when the tower bisects an angle of ninety degrees in the line. When the angle in the line is as large as ninety degrees, it will often be more desirable to construct a special tower, and to set it normal to the direc- tion of the line. SPECIAL TOWERS Having determined whether it will be necessary to provide special towers to take care of angles in the line, the next step should be to determine how many, if any, special towers should be provided to take care of such special cases as railroad crossings, and what specifications must govern in the design of these special structures. The Railroad Companies have their own specifications for these structures, and they Transmission Towers 47 Value of COMPONENT Y fir tension of 1000 Ib. in win (tor Condition A. For Condition B the components balance and their sum 'a zero) TRANSVEBX AHD Lff COMPONENTS ANGLE TOWERS B/sfcr THf AHGLC IH THE LINE too too ioo4ooxo60oioo6oo9oo 1000 (Condition A] tOO *W tOO 800 IOOO ItOO MOO I6OO 1800 tOOO / Value of COMPONENT X for tension of IOOO Ik in wire. Fi*. 11 48 Transmission Towers insist that all wires carried over their crossings shall be supported by structures complying with all their requirements as to loadings and unit stresses to be employed. Their specifications are generally very severe and, hence, special designs almost always are required for those particular points in the line. Of course, one thing always to be kept in mind, is to make as few different designs as circumstances will allow, so that there will be as much duplication as possible in the structures. This is an especial advantage for economical fabrication in the shop, and is also a big advantage when it comes to erecting the towers in the field. Every line must be carefully studied and designed for its own particular requirements. A line w r hich is taken through a city must be built in a different way from one going through an open country. The working loads might not need to be any heavier, but either the design loads should be heavier or the unit stresses lower, and the towers should be spaced closer together. REGULAR LINE TOWERS The average line of any length should have three different types of towers. These may be designated as Standard or Straight Line, Anchor, and Dead End Towers. All towers should be designed to take care of the dead weight of the structures and also the vertical loads at the ends of all the cross arms, in addition to and simultaneously with, the horizontal loadings speci- fied below. STANDARD TOWERS The Standard, or Straight Line, Towers should predominate, and should be designed to support without failure the required horizontal loads transverse to the direction of the line, combined with a horizontal pull in the direction of the line applied at any one insulator connec- tion equivalent to the value of the wire when stressed to about one-half its ultimate strength. These loads transverse to the line should be large enough to include the wind load across the wires and that against the tower itself, with a little margin of safety. ANCHOR TOWERS The Anchor Tower should be designed to support without failure any one of the following horizontal loadings: Transmission Towers 49 (1) The same horizontal loads as those specified for the Standard Tower. (2) An unbalanced horizontal pull in the direction of the line equiva- lent to the working loads of all the conductor wires and the ground wires, applied at the points of connection of the wires to the tower, combined with the transverse horizontal loads on the wires and the tower. (3) An unbalanced horizontal pull parallel to the line equivalent to the working loads of the wires, applied at one end of each cross arm, all on the same side of the tower and all acting in the same direction, combined with the horizontal transverse loads on the wires and the tower. DEAD END TOWERS The Dead End Towers should be designed to support the same load- ings as those specified for the Anchor Towers, but the sections should be determined by using smaller unit stresses. Unit stresses of 18000 pounds per sq. in. in tension and 18000 60 -=r for compression, would give these towers approximately 50% more strength than the anchor towers would have when stressed just within the elastic limit. It will be noted that under the above specification, the standard tower will be required to take care of the torque resulting from an un- balanced horizontal pull equivalent to the allowable tension (which is one-half the ultimate strength) of one wire, applied at one end of any cross arm and acting parallel to the. direction of the line; while, the anchor and the dead end towers are both required to take care of either the torque as given above for the standard tower or the torque result- ing from an unbalanced horizontal pull equivalent to the working loads (actual tension in the wire under the working conditions) of all the wires on either side of the center line of the tower, applied at one end of each of the cross arms, and all acting parallel to the line and in the same direction. If one anchor tower is placed in the line for every ten or twelve standard towers, all conditions resulting from broken conductor wires should be localized to the territory between two an- chor towers. The reason for using lower unit stresses in the dead end towers than in the anchor towers for exactly the same loadings, is that the dead end towers may have to support a large part of this total load- ing at all times, and all of it very frequently, while the anchor tower 50 Transmission Towers may have to support the same loading only once in a great while, and then for only a very brief time. One of the aims to be kept constantly in mind in designing a trans- mission structure, is to get a finished tower in which all the stresses can be determined definitely. We usually determine the stresses graphic- ally. The stresses resulting from the horizontal loads applied as so much shear must be determined separately from the stresses resulting from torque. These stress diagrams cannot be combined except in those cases where the slope of the post does not change between the horizontal planes bounding that part of the tower for which the dia- grams are wanted. This is true because the horizontal loads which act as so much shear, may be assumed to be acting in a plane containing both posts of the face of the tower, parallel to the direction of the load, in which case the posts may or may not (depending upon the slope of the posts) take up a part of this shear directly. On the other hand, the torque is a moment acting in a horizontal plane and is constant between any two parallel planes, unless it is either increased or de- creased by an additional torque of the same or opposite kind. ANCHORAGE DESIGNS The members for anchoring the structure to the footings are gener- ally the last part of the design to be considered. The first question to be determined is whether concrete footings shall be used. These are more simple, and involve much less steel work than any other type of footing used for transmission line structures. The weight of the concrete itself reacts against the tendency of the post to pull away from the base because of the tension in the post on one side of the tower. It also offers more bearing surface against the earth around the footings and introduces the passive resistance of a larger volume of earth against the uplifting tendency of the post on the ten- sion side of the tower. Of course, the saving in the cost of steel in the structure must be balanced against the expense involved in putting the concrete in place, to determine whether or not it is advisable to use concrete footings. This will depend upon many circumstances which must be very carefully considered before reaching a conclusion. It is impossible to overestimate the importance of good anchorages. An otherwise excellent construction may be made inadequate by using footings which are not substantial. If one of the footings should be Transmission Towers 5plice ang/e Concrete - Anchor bolts, 40to50diam. in concrete Concrete Anchors Concrete pad- Anchor grouted in drilled holes. Rock Anchor Splice angk^& Ground line^ Earth Anchor Fiji. 12 52 Transmission Towers insufficient to take care of the loads for which the superstructure is intended, it would be very apt to yield under full loading, and, in doing so, would bring about a new distribution of stresses among the mem- bers, and would put on some of the members stresses which were not in keeping with those for which the members were designed. Such a re- arrangement of stresses may very easily be so vital as to bring about the failure of the superstructure. In view of this fact, it is recom- mended that, where there is any doubt as to whether concrete footings should be used, the benefit of any small doubt should always be given in favor of such footings. But, it may be that the structures are to be used where such footings would be practically impossible. Under such circumstances, other provisions must, of course, be made. In the case of poles, the regular outline is generally continued below thie surface of the ground whether concrete footings are used or not; but if concrete is not used, then additional steel must almost always be used to get more bearing area against the earth. In the case of towers there is provided a separate footing for each of the posts. When concrete footings are used the posts are connected to them in one of two ways: In the first method, extensions of the post sections, which are called anchor stubs, may be built in these footings with just sufficient length extending above the concrete so that the lower post sections of the tower may be connected directly to them. These anchor stubs may extend almost to the bottom of the footing, or they may extend into the footings only far enough that the adhesion of the concrete to them will develop their full strength, in which case it will be necessary to add steel reinforcing bars from this point to the bottom of the concrete. This is necessary because provision must be made to bind the concrete together so that it will not break apart under the uplifting force in the post, and thus defeat its purpose. The other method used with the concrete footing is to have a base at the lower end of the post section which will bear directly on the mass of concrete in the footing, and which will at the same time be connected directly to this concrete by means of long bolts or rods extending well into the mass of concrete. These rods, in this case, would be brought into action only when the post is under tension. If these rods are straight for their full length, and fairly large, they should be imbedded in the concrete for a length equal to fifty times their diameter, in order to develop their full breaking strength. But if these rods are bent a little near their lower ends, their breaking strength will be developed Transmission Towers 53 by imbedding them in the concrete for a length equal to forty times their diameter. Provision for binding together the concrete in the footing must be made when anchor rods are employed, just the same as when anchor stubs are used. With any type of footing, there must be provided sufficient bearing surface against the earth to resist the maximum compression in the post, and also an arrangement to lift enough earth to resist the maxi- mum uplifting tendency in the post under the worst condition of loading. The most positive and direct way to determine the size and outline of a footing for any given loading, is to increase this loading by the desired factor of safety, and then to determine a footing of which the ultimate resisting value will be sufficient to meet the conditions to be imposed. We recommend that the footing be so designed that its ultimate resisting value will be not less than 25% in excess of what is necessary to sustain the loading specified for the pole or tower. For specially heavy towers which are required to dead-end heavy wires on long spans, it sometimes becomes a troublesome matter to provide adequate footings to take care of the uplift from the posts on the tension side of the tower under the assumed condition of maximum loading. This often happens in the case of ^River-Crossing Towers. Footings for such cases, if built in the ordinary way, would have to be made very deep and would require a large amount of concrete. It will often be found to be economical to design these footings with special outline and construction. The following rather unique method has been successfully employed for taking care of cases involving unusually large uplifts, when the footings are built in clay or in mixed clay and sand that is compara- tively free of gravel. A square pit is dug deep enough that its bottom will be below the frost line and large enough to afford sufficient bearing area against earth to sustain any possible downward pressure where the tower post may be subjected to either tension or compression. In the center of this pit a hole about twenty inches in diameter is bored with an earth-auger to the depth desired (this depth has been made as much as twenty feet below the bottom of the square pit). Dynamite is then placed in the bottom of this hole and connected with a firing magneto; then the hole is filled with concrete of 1 :2 :4 mixture, medium wet, and the charge of dynamite is fired immediately. The charge of dynamite that is generally used for this purpose consists of eight one- 54 Transmission Towers half pound sticks of 60% dynamite. Reinforcing bars with their ends bent are then pushed down through the concrete to the bottom of the hole and then raised three inches and securely held in this position to prevent them from sinking through the concrete and coming in con- tact with the earth before the concrete has set. The hole is then re- filled with concrete, and the footing in the square pit is also poured and finished. From the moment the dynamite is placed and connected with the firing magneto, it is essential that all the subsequent opera- tions be conducted as rapidly as possible. Not more than five minutes should be allowed between the time when the first pouring of concrete is started and when the dynamite is fired. The average displacement from such an explosion of dynamite is about one and one-half cubic yards, this, of course, being dependent upon the depth of the hole and the nature of the surrounding earth. Experimental footings placed in this manner show that the enlarged base takes an almost spherical form with its center above the bottom of the excavated hole a distance equal to about one-fourth the horizontal diameter of the enlarged base. This diameter is sometimes almost four feet. It is evident that a footing of this kind can be made to resist a very large uplifting pull. In the case of light towers it is sometimes considered advisable to put the tower in its erect position above the ground before the anchors are set, and to then bolt these footing members to the lower end of the main tower legs and put concrete or earth back fill around them while the tower is being supported independent of them. But in the case of heavy towers it is generally considered more economical to set the foot- ing members exactly in their position first, and to then erect the towers and connect them to their footings. This latter method of erection requires that the anchor stubs be aligned as accurately as possible, as any inaccuracy in the setting of these anchors will make the subsequent assembling of the tower more difficult and less satisfactory. If the anchor stubs are not set accurately to their true positions, there will be introduced in the tower, additional stresses for which the tower mem- bers were not designed. An accurate alignment of the anchors can be accomplished only by using rigid templates that will hold the anchors in their definite positions until they have been secured by either the back fill or concrete. Almost all towers are built smaller at the top than at the ground line, and the tower leg inclines from the vertical as determined by this Transmission Towers 55 outline of the structure. The anchor stub generally follows the. direc- tion of the main tower leg, but when it is put in this position and sus- pended from a template it has a tendency to swing to the vertical position. To obviate this condi- tion the setting template should be trussed as shown in Fig. 13. TCMPLATT fOK ANCHORS aoft pests art ^^^L Fig. 13 ERECTION Transmission towers are erected in one of two ways: they may be erected by assembling the members one at a time in their proper positions in the com- pleted structure, or by assemb- ling the complete structure in a prone position, and raising it to its vertical position by swinging it about two hinge points on or near two anchor stubs. If the first of these two methods is used, there will generally be re- quired a crew of eight men, including one foreman. The following equipment will generally suffice: One light gin-pole, about 25 feet long. One set of two-sheave and three-sheave blocks for % * diameter rope. About 300 feet of %" diameter rope; four hand lines, each about 150 feet long; four small gate blocks for the hand lines. The post members are erected with the gin-pole and tackle, but all the other members are pulled up from the ground with the hand lines. The time required will be about the same whether the tower is light or heavy. The time required will, however, depend upon both the accuracy of the fabrication of the material and the accuracy of the alignment of the anchor stubs. If the second method is used, the actual work erecting the tower does not consume more than ten or fifteen minutes after all the prepara- tions have been made. These preparations and the erection consist of three distinct operations: (1) Leveling the ground where required for the erection equipment, and blocking up the tower on rough ground and for side-hill extensions. A crew of seven or nine men including a foreman is required. 56 Transmission Towers (2) Rigging up erection equipment, and bolting erection shoes and struts in place, etc. A crew of about twelve men including a foreman is required. (3) The actual raising of the tower. Sometimes horses are used for this operation, but it is often found to be more satisfactory to use a caterpillar tractor, especially for raising the heavier towers. One team of horses will generally suffice for this work, but it often requires four and sometimes six horses especially in rough country and for raising towers that are unusually heavy. The Tractor gives a much steadier pull, and will permit of holding the load at any desired point more satisfac- torily than when horses are used. A substantial A-- frame usually built up of steel pipes is generally em- ployed for raising the tower from the prone to the up- right position. A steel cable should also be used in preference to a manilla rope for this purpose in the case of the heavier towers. When concrete footings are used, and this method of erection is em- ployed, there is an advantage in having the anchor stubs set and con- creted in position in advance of the assembling of the tower. When this is done, the tower can be assembled close to the anchor stub and can be raised about hinges fastened to the tops of the anchor stubs; but when the tower is assembled before the concrete is placed around the anchor stubs, it is necessary to assemble the tower a few feet away from the stubs, and then to skid the tower into the position from which it is to be raised. This process of skidding the tower is costly, and is also likely to injure the tower members. SPACING OF TOWERS The trend of American practice today in the designing of transmis- sion line installations is to make the spans between supporting struc- tures as great as possible. As the result of considerable study extend- ing over several years of experience with lines having spans some of which were very short while others were exceptionally long, it has been determined that the best and most economical lines, all things con- sidered, are those in which the supporting structures are spaced far apart. Transmission Towers 57 This is true even though the first investment for the original installa- tion is somewhat larger in the case of long spans than where short spans are used. It has been determined from comparative records that the maintenance of lines having the long spans is much less than was the maintenance of the same lines during previous periods when shorter spans were used. This decreased cost of maintenance has been proved to be sufficiently important to warrant making larger initial investments on original projects. The maintenance is not only less expensive with the long spans but it is also less troublesome, because there is less interference with continuous service along the line. This is a matter worthy of careful consideration, as the value of elec- trical service in almost every case is dependent upon the assurance of its continuity. By using long spans the number of insulators required is reduced; and, as there is always a chance that a flash-over will occur at the insulator, it is obviously advisable to reduce the number of insulators to a minimum in order to eliminate, as far as possible, this source of trouble for the service. Another advantage derived from the use of long spans is that the variations of stress in the wires resulting from large changes in tem- perature will be much less than under similar conditions of loading on short spans. The constant changing of stress in the wires is produc- tive of more trouble than higher stresses which are more uniformly applied. The long span is especially advantageous for a line carried along a hillside, because it will generally permit of such an arrangement of towers that there will not be any upward pull on any of them. The upward pulls are always a source of trouble, and they should be elim- inated wherever conditions will permit an alternative construction. The upward pull causes not only mechanical but also electrical troubles, because, during a rain storm, water will run down along the wire into the insulator, which, of course, immediately produces electrical trouble. The voltages used on present day high tension lines are such that the suspension-type and strain-type insulators are rapidly displacing the pin-type insulators. This, of course, means longer and heavier cross arms and higher supporting structures. It is also true that the cost of wood is steadily increasing, and will continually increase as the wood becomes less plentiful. These conditions when combined with the tendency for long span construction as described above, mean that 58 Transmission Towers the wood pole construction is being rapidly superseded by the better and more permanent steel tower construction. When the Manufacturer is expected to design the structures for a line of any considerable length, he is generally furnished very definite and complete specifications regarding loadings and unit stresses; but when he is asked for quotations on only a few structures, it is not often that full and complete information regarding working conditions are furnished him. Nor will this information always be forthcoming, even when the customer is requested to give more definite data. As a rule, a part of the necessary information will be furnished by the cus- tomer, and it becomes the task of the Manufacturer to complete the design by making his own assumptions regarding the missing data. The customer will very often profit financially by making as com- plete as possible the information he gives to the Manufacturer, and it is always much more satisfactory to the designer to know positively what working conditions are to determine the design. Transmission Towers 59 | M Ultimate Strength Lbs. pe Square In. I oooooooo 88-8888 O ON CN oo cc cs ro ^ PC CN OO c u a rt cd c % . 1 i i _ 3 1 "E en C c a *T fi! O/! S S 1 i i 2 en en en uT uT uT a a a O O. f"V ooo U U U ? TD a> o f "g c s s -,- -M 5 j -S : g c 3 i: G en 1 1 .G g | G S, *G _T - - a o a U < ry^ &J3 ^3 "^ o 0> M o ^; *3 oo - lt: M ^^ CJ CJ s +".", 8 "S ^^ * ^ + 4- o-o-o 111 bo bfl bfl .S .S .S 3 -5 -3 J| 8 < PQ U U U U 60 Transmission Towers | 8 8 8 8 8 w w| ro to 3 NO IO J co 04 ** ^ 18 OJ 3-g 00 01 ^ CO OC CO 00 01 to 01 s H eoi S s|i ?=l NO 00 0^ oo NO to rO * 3 o CO ^ $ felr 1 i % ON CO to CN ON to oo o*S ^ 3 & oo "* *" *S PER LIN. VERTICAL H I* o 01 to CN OJ Ol ro s CN Os 00 to T i I! 1 Ol . oo CO 3 to o CN ^ t cs 9 o s < 2 i II o o to o 10 | 8 1 H T 55 01 1 o\ *^ O <* i H | ~$ 8 8 8 8 8 tu 5 to OJ OJ CO % 00 5 v 45 C^ g H Is 8 to IO 8 IO 8 1 s 3 S 0 "* * 01 SIEMENS | i 8 10 8 c_ 8 ON" oq_ '| d NO to 0) 01 CO 3 01 01 CO q q I 1 1 NO IO 0) 10 1 o 10 ro >o OJ CO ' i 3? B X H2 ^ * Transmission Towers 61 ed B TABLE 3 re Stran MAX. LOAD PER LIN. FOOT PLANE OF RESULTANT LIN. F ONTAL D PE HOR R LIN. RTICAL w \o o~ ic ** ~r ~i *^r ^r * * * OOO^I^J O *O *! O r*l 00 O %J r~ o So 10 * * -4 10 rs 10 > *9 W> * 'S CM rs ro <> "5 "5 * ^t^'^ui 10 u^ 10 10 f-a p^-^p G>OO- CQ U J ^i ci rvi . O 10 u ? T t'* f *? t *? c 1 r 1 c 1 odd dddd dddd dddd O\l~ i/} 1 ^ OJOOO'O ^f*5CN^ *-^OO^O^ 3 'S fS ! r-.' ' OO rs?N dddd dddd u^dOOC iOfS>O<*5 vOCSU-!ro O t^ O _;^^ dddd dddd dddd _. |||g 111 g|S iSil . S8 8S SSS S88 S t^.\O^}fS ^OO> in O> O O* OT 00 rC 10 W) ro" rf OOOO OOOO OOOO OOOn T O O o^r^ i^i--.^JC W< oT I>T o o > o "> 62 Transmission Towers ** oo io io ro CM" i~" O\ 00 CM ON ON -< * ON l^ NO Tj CO fO CM 8 8 222" 3 3 s;? *S 2 S ON 2- ?0 ^f ri io io >o MAX. LOAD PER LIN. FOOT PLANE OF RESULTANT u U CM 1O 1^- tf) fN O f: ro 10 fO CN 2 q q ON ON ON ' ^ -,4 d do ^ ro eo CM o o o o LIN. F ONTAL AD P HO 3*6* O* *5 O l^ o ^ >o t^ * " 00 VO VO NO IO 10 gfgg dodo o oo o to oo >o NO fO CM O CO t^ oo oo oo oo !> t>. dodo do 10 r-i o o t^ ^H in o O O 't "* 6600 CM CM t-^ IO 1-^ CO NO CM OO IO CM O "5 PO CM CM CM CM d d d d do " CM Tt< r^ NO co CM ~ O O ON ON ~ ** ' ~' do 00 * O *5 f^ (^ 5? pr, N O ON 00 4 N d e ^- NO NO IO IO 't d d d d do * O O <^J . "J *. ^ 0000 CO CM 0> NO O 0> O O IO fN O t^ CM CM ~ ~4 ^ O d d d d do 11 000 o o >o O >O O >O O 00 M t^ ^ gg s O O VO >O HARD DRAW O O O O -H O\ tN >O rO O CM ID oo" o * CM OO NO NO Tjt H Tj< ON IO CM ro" CM" ^<" -*" *+ sss ss 0000 0000 00 OO>OIO ONOCON'J' CMCM do'dd dodo do popo M o -* o\o Transmission Towers 63 u l- iO so * PN * 10 00 iO O'* CN IO Os 00 lOCsOOfN SO O O Os Os PN O r~~ -f 10 O O Tf I- SO O O -H PO 00 O Os 00 -H sO CN sO CN 00 ^^ -i o o 55 Q2=l O t^ Os t^ *-> O fN OO <* -+ 00 Tj< Os iO 00 t^ -rt* 10 -H -H 10 ^ -H \O >O CS - 1 Os 00 ! ^t * ro Os fS to % $ 3 oooo o so O fO so O oooo oooo OO'-iCvlOs OvOTjO ^ Ol ^^ ^ "^ -i Os o . ^* iO *"^ vO ^^ f} CXI OO *O Os t** ^^ PO OO ^^ sO Os >O i t- POO'sOPC OOOsOtO ^POCNfN P^POCOCN PN -H 000 OOOO O O 00 O CN iO OO O O Os Os 00 t^- I*- i O M CO -* 10 o o o o o o IT) O O M* ^- f*5 **5 CM 64 Transmission Towers CQ oc i i i d & .& *c 2 *o i i a MAX. LOAD P LIN. FOOT PLA OF RESU D PER LIN. HORIZONTA IN. CAL D P V s II ON OO IN NO i-tfOO-* NOON lOOf^f^ IO tO NO C4 * CN NO -* NO fO O 00 NO O * tO t-~ t^ 00 >O NO O ^ to n* OO ON ^ ON ^> NO 00 OO NO <* Tj< ts OOO -i s<:s 2^S^ l?^ ^ -iOOO OOOO OO ON a 00 00 t- f^ t^ r-. NO >0 to" to" ^ PC O OO NO vO to OO PC t- O r- t- ^ O PC PO PO N NO IO IO 00 to ON t tO ON O i-" <* 01 iO PC O NO PC O 00 NO 111 t^ rt< to to iO to O PC OO to -H pvl PC f ON 00 00 t^ t- Ov 00 to CM P>< 00 N NO tO IO Tj< 00 O N >O Tj OO O O CN IO O CN PC ^i- 00 ON 00 N to O t^- NO to O o o o ** o o o to o to *-> o to 66 Transmission Towers SAGS In the following tables are given sags at which conductors shall be strung in order that, when loaded with the specified requirement of one-half inch of ice and a wind load of 8.0 pounds per square foot of projected area at degrees Fahrenheit, the tension in the conductor will not exceed the allowable value of one-half the ultimate strength of the conductor as given in preceding tables. The sags given in the tables for 120 degrees Fahrenheit are greater in every case than the vertical component of the sags at degrees Fahrenheit under the maximum wind and ice load. Transmission Towers 67 Minimum Sags for Stranded Hard -Drawn Bare Copper Wires No. 4/0 B. & S. SPAN IN FEET F. 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Inches Feet Feet Feet 20 2 3 5 8 13 20 3.5 6 10 2 4 5 9 14 22 3.5 6.5 10.5 20 3 4 6 10 16 24 4 7 11.5 40 3 4 6 11 18 27 4.5 8 12 60 3 5 7 13 20 31 5 8.5 13 80 4 6 8 15 24 35 5.5 9 13.5 100 4 7 10 17 27 40 6 10 14.5 120 5 8 12 20 31 46 7 10.5 15 No. 3/0 B. & S. SPAN IN FEET F. 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Inches Feet Feet Feet 20 2 3 5 8 13 21 4 7 12 2 4 5 9 15 23 4 7.5 12.5 20 3 4 6 10 17 25 4.5 8.5 13.5 40 3 4 6 12 19 29 5 9 14 60 3 5 7 13 22 33 6 9.5 15 80 4 6 8 15 25 38 6.5 10.5 15.5 100 4 7 10 18 29 43 7 11 16 120 5 8 12 21 34 49 7.5 12 17 No. 2/0 B. & S. SPAN IN FEET 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Inches Feet Feet Feet 20 2 3 5 9 14 23 4.5 9 15 2 4 5 10 16 26 5 9.5 15.5 20 3 4 6 11 18 29 5.5 10 16 40 3 4 7 12 21 33 6 11 17 60 3 5 7 14 24 37 6.5 11.5 17.5 80 4 6 9 16 28 43 7 12 18 100 5 7 10 19 32 48 8 12.5 18.5 120 6 9 12 23 37 54 8.5 13.5 19.5 No. B. & S. SPAN IN FEET 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Feet Feet Feet % Feet 20 2 3 5 9 16 2.5 5.5 11.5 18.5 2 4 5 10 18 2.5 6.5 12 19 20 3 4 6 11 21 3 7 12.5 19.5 40 3 5 7 13 24 3.5 7.5 13 20 60 3 5 8 15 27 4 8 14 20.5 80 4 6 9 18 32 4.5 8.5 14.5 21.5 100 5 7 11 21 ' 37 5 9 15 22 120 6 9 13 25 42 5 9.5 15.5 22.5 68 Transmission Towers Minimum Sags for Solid Hard -Drawn Bare Copper Wire No. 1 B. & S. SPAN IN FEET Temp. F. 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Feet Feet Feet Feet 20 2 4 5 10 19 3 8 14.5 23 3 4 6 11 22 3.5 8.5 15 23.5 20 3 4 6 13 25 4 9 16 24 40 3 5 7 15 30 4.5 9.5 16 24.5 60 4 6 8 18 34 5 10 17 25 80 4 7 10 21 39 5.5 10.5 17 25.5 100 5 8 12 25 44 6 11 18 26 120 6 10 16 30 49 6 11.5 18 26.5 No. 2 B. & S. SPAN IN FEET 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Feet Feet Feet Feet 20 2 4 5 12 25 4 10.5 18.5 29 3 4 6 14 29 4.5 11 19 29.5 20 3 5 7 16 33 5 11.5 19.5 30 40 3 5 8 19 39 5.5 12 20 30.5 60 4 6 10 23 43 6 12.5 20.5 31 80 4 7 12 27 48 6.5 13 21 31 100 5 9 14 31 53 7 13 21.5 31.5 120 7 11 18 35 58 7.5 13.5 22 32 No. 3 B. & S. SPAN IN FEET Temp. 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Feet Feet Feet Feet Feet 20 3 4 6 17 3 6 14 24 37.5 3 4 7 20 3.5 6.5 14.5 24.5 37.5 20 3 5 8 23 4 7 15 25 38 40 3 6 10 27 4.5 7.5 15 25 38 60 4 7 12 30 5 8 15.5 25.5 38.5 80 5 9 14 35 5.5 8.5 10 26 39 100 6 11 17 39 5.5 8.5 16.5 26 39 120 8 14 22 44 6 9 16.5 26.5 39.5 No. 4 B. & S. SPAN IN FEET Temp. F. 100 or Less 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Feet Feet Feet Feet Feet 20 3 4 8 25 5 9 18 31 46 3 5 9 29 5.5 9 18.5 31.5 46 20 3 6 11 33 6 9.5 19 31.5 46.5 40 4 7 13 38 6.5 10 19 32 46.5 60 4 9 16 42 6.5 10 19.5 32.5 47 80 5 11 19 46 7 10.5 19.5 32.5 47.5 100 7 13 23 50 7.5 11 20 32.5 47.5 120 9 16 27 54 7.5 11 20.5 33 48 Transmission Towers 69 Minimum Sags for Stranded Bare Aluminum Wires No. 4/0 B. & S. SPAN IN FEET Temp. F. 80 or Less 100 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Feet Feet Feet Feet Feet 20 1 2 3 S 11 2.5 5 11 19 29 1 2 3 6 15 3 5.5 12 19.5 29.5 20 2 3 5 8 21 3.5 6 12.5 20.5 30 40 2 4 7 11 27 4.5 7 13 21 31 60 4 6 11 17 34 5 7.5 13.5 21.5 31.5 80 6 10 16 22 41 5.5 8 14 22 32 100 10 14 20 27 46 6 8.5 14.5 22.5 33 120 13 18 25 32 52 6.5 9 15 23 33.5 No. 3/0 B. & S. SPAN IN FEET Temp. F. 80 or Less 100 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Inches Feet Feet Feet Feet Feet 20 1 2 3 5 12 3 5.5 13 22 33.5 1 2 4 6 17 3.5 6.5 13.5 22.5 34 20 2 3 5 8 24 4.5 7 14 23 34.5 40 2 4 7 12 31 5 7.5 14.5 23.5 35 60 3 5 11 18 38 5.5 8 15 24 35.5 80 6 9 16 23 43 6 8.5 15.5 24.5 36 100 10 13 20 29 49 6.5 9 16 25 36.5 120 13 17 25 33 54 7 9.5 16.5 25.5 37 No. 2/0 B. & S. SPAN IN FEET Temp. F 80 or Less 100 125 150 200 250 300 400 500 600 Inches Inches Inches Inches Feet Feet Feet Feet Feet Feet 20 1 2 3 6 2 5 8.5 16.5 28 42 2 2 4 8 2.5 5.5 9 17 28.5 42.5 20 2 3 6 12 3 6 9 17.5 29 43 40 2 4 9 18 3.5 6.5 9.5 18 29.5 43 60 4 7 14 24 4 7 10 18.5 29.5 43.5 80 7 12 19 29 4.5 7 10.5 19 30 44 100 10 16 24 33 5 7.5 11 19.5 30.5 44.5 120 14 19 28 38 5.5 8 11.5 20 31 44.5 No. B. & S. SPAN IN FEET Temp. F. P 80 or Less 100 125 150 200 250 300 400 500 Inches Inches Inches Inches Feet Feel Feet Feet Feet 20 1 2 4 9 3.5 7 10.5 21 36.5 2 3 6 14 4 7 11 21.5 36.5 20 2 4 8 20 4.5 7.5 11.5 22 37 40 3 6 13 26 5 8 12 22 37 60 5 10 18 31 5 8.5 12 22.5 37.5 80 8 14 23 35 5.5 8.5 12.5 23 38 100 12 18 27 39 6 9 13 23 38 120 15 21 31 43 6 9.5 13.5 23.5 -38.5 70 Transmission Towers GALVANIZING IRON AND STEEL We recommend the specifications adopted by the National Electric Light Association, which are as follows: These specifications give in detail the test to be applied to galva- nized material. All specimens shall be capable of withstanding these tests. a Coating The galvanizing shall consist of a continuous coating of pure zinc of uniform thickness, and so applied that it adheres firmly to the sur- face of the iron or steel. The finished product shall be smooth. b Cleaning The samples shall be cleaned before testing, first with carbona, benzine or turpentine, and cotton waste (not with a brush), and then thoroughly rinsed in clean water and wiped dry with clean cotton waste. The samples shall be clean and dry before each immersion in the solution. c Solution The standard solution of copper sulphate shall consist of commercial copper sulphate crystals dissolved in cold water, about in the propor- tion of 36 parts, by weight, of crystals to 100 parts, by weight, of water. The solution shall be neutralized by the addition of an excess of chemically pure cupric oxide (Cu O). The presence of an excess of cupric oxide will be shown by the sediment of this reagent at the bot- tom of the containing vessel. The neutralized solution shall be filtered before using by passing through filter paper. The filtered solution shall have a specific gravity of 1.186 at 65 degrees Fahrenheit (reading the scale at the level of the solution) at the beginning of each test. In case the filtered solution is high in specific gravity, clean water shall be added to re- duce the specific gravity to 1.186 at 65 degrees F. In case the filtered solution is low in specific gravity, filtered solution of a higher specific gravity shall be added to make the specific gravity 1.186 at 65 degrees Fahrenheit. As soon as the stronger solution is taken from the vessel containing the unfiltered neutralized stock solution, additional crystals and water must be added to the stock solution. An excess of cupric oxide shall always be kept in the unfiltered stock solution. Transmission Towers 71 d Quantity of Solution Wire samples shall be tested in a glass jar of at least two (2) inches inside diameter. The jar without the wire samples shall be filled with standard solution to a depth of at least four (4) inches. Hardware samples shall be tested in a glass or earthenware jar containing at least one-half (J/) pint of standard solution for each hardware sample. Solution shall not be used for more than one series of four immer- sions. e Samples Not more than seven wires shall be simultaneously immersed, and not more than one sample of galvanized material, other than wire, shall be immersed in the specified quantity of solution. The samples shall not be grouped or twisted together, but shall be well separated so as to permit the action of the solution to be uniform upon all immersed portions of the samples. f Test Clean and dry samples shall be immersed in the required quantity of standard solution in accordance with the following cycle of immersions. The temperature of the solution shall be maintained between 62 and 68 degrees Fahrenheit at all times during the following test. First Immerse for one minute, wash and wipe dry. Second Immerse for one minute, wash and wipe dry. Third Immerse for one minute, wash and wipe dry. Fourth Immerse for one minute, wash and wipe dry. After each immersion the samples shall be immediately washed in clean water having a temperature between 62 and 68 degrees Fahren- heit, and wiped dry with cotton waste. In the case of No. 14 galvanized iron or steel wire, the time of the fourth immersion shall be reduced to one-half minute. g Rejection If after the test described in Section "f" there should be a bright metallic copper deposit upon the samples, the lot represented by the samples shall be rejected. Copper deposits on zinc or within one inch of the cut end shall not be considered causes for rejection. In the case of a failure of only one wire in a group of seven wires immersed together, or if there is a reasonable doubt as to the copper deposit, two check tests shall be made on these seven wires, and the lot reported in accordance with the majority of the set of tests. 72 Transmission Towers USEFUL DATA Given, ax 2 + bx -f c = 0; X -b =fe V b 2 4 ac 2a e = Base of Napierian Logarithms = 2.7182818285 Log ]0 C = 0.4342944819 (e v V^ V 3 + ^ V 7 4- V 8 + + V 9 + V 5 IE One inch = 2.540005 centimeters One centimeter = 0.3937 inches One foot = 0.3048006 meter One meter = 3.2808333 feet One pound (avoirdupois) = 0.45359 kilograms One pound per foot = 1.488161 kilograms per meter. One pound per square inch = 0.0703067 kilograms per square centi- meter One inch-pound = 1.152127 kilogram-centimeters One kilogram per meter = 0.67197 pounds per foot One kilogram per square centimeter = 14.2234 pounds per square inch One kilogram-centimeter = 0.86796 inch-pounds Trigonometrical Formulae Radius, 1 = sin 2 A -f cos 2 A = sin A cosec A = cos A sec A = tan A cot A cos A 1 . , * ^ / ! -- cotan A *j sine rt T cot A A sin A cosec A K .-^^ X \ ver. in A /__ Cosine Tangent I 5 Cotangent -l_.i Secant Cnsprant r cin A rot A \/ 1 cin 2 A tan A . sin A sec A = =sin A sec A cot A f AqkleA j~~* A - cos A cos A sin A A _ tanA ~ tan A 1 * radius -i J sin A A cotA cos A 1 Transmission Towers NATURAL TRIGONOMETRIC FUNCTIONS 73 Degrees Sines Cosines Tangents Cotangents Secants Cosecants Degrees 1 2 3 0.00000 0.01745 0.03490 0.05234 1.00000 0.99985 0.99939 0.99863 0.00000 0.01746 0.03492 0.05241 57.28996 28.63625 19.08114 1.00000 1.00015 1.00061 1.00137 57.29869 28.65371 19.10732 90 89 88 87 4 5 6 7 0.06976 0.08716 0.10453 0.12187 0.99756 0.99619 0.99452 0.99255 0.06993 0.08749 0.10510 0.12278 14.30067 11.43005 9.51436 8.14435 1.00244 1.00382 1.00551 1.00751 14.33559 11.47371 9.56677 8.20551 86 85 84 83 8 9 10 11 0.13917 0.15643 0.17365 0.19081 0.99027 0.98769 0.98481 0.98163 0.14054 0.15838 0.17633 0.19438 7.11537 6.31375 5.67128 5.14455 1.00983 .01247 .01543 .01872 7.18530 6.39245 5.75877 5.24084 82 81 80 79 12 13 14 15 0.20791 0.22495 0.24192 0.25882 0.97815 0.97437 0.97030 0.96593 0.21256 0.23087 0.24933 0.26795 4.70463 4.33148 4.01078 3.73205 .02234 .02630 .03061 1.03528 4.80973 4.44541 4.13357 3.86370 78 77 76 75 16 17 18 19 0.27564 0.29237 0.30902 0.32557 0.96126 0.95630 0.95106 0.94552 0.28675 0.30573 0.32492 0.34433 3.48741 3.27085 3.07768 2.90421 1.04030 1.04569 1.05146 1.05762 3.62796 3.42030 3.23607 3.07155 74 73 72 71 20 21 22 23 0.34202 0.35837 0.37461 0.39073 0.93969 0.93358 0.92718 0.92050 0.36397 0.38386 0.40403 0.42447 2.74748 2.60509 2.47509 2.35585 1.06418 1.07115 1.07853 1.08636 2.92380 2.79043 2.66947 2.55930 70 69 68 67 24 25 26 27 0.40674 0.42262 0.43837 0.45399 0.91355 0.90631 0.89879 0.89101 0.44523 0.46631 0.48773 0.50953 2.24604 2.14451 2.05030 1.96261 1.09464 1.10338 1.11260 1.12233 2.45859 2.36620 2.28117 2.20269 66 65 64 63 28 29 30 31 0.46947 0.48481 0.50000 0.51504 0.88295 0.87462 0.86603 0.85717 0.53171 0.55431 0.57735 0.60086 1.88073 1.80405 1.73205 1.66428 1.13257 1.14335 1.15470 1.16663 2.13005 2.06267 2.00000 1.94160 62 61 60 59 32 33 34 35 0.52992 0.54464 0.55919 0.57358 0.84805 0.83867 0.82904 0.81915 0.62487 0.64941 0.67451 0.70021 1.60033 1.53987 1.48256 1.42815 1.17918 1.19236 1.20622 1.22077 1.88708 1.83608 1.78829 1.74345 58 57 56 55 36 37 38 39 0.58779 0.60182 0.61566 0.62932 0.80902 0.79864 0.78801 0.77715 0.72654 0.75355 0.78129 0.80978 1.37638 1.32704 1.27994 1.23490 1.23607 1.25214 1.26902 1.28676 .70130 .66164 1.62427 .58902 54 53 52 51 40 41 42 43 0.64279 0.65606 0.66913 0.68200 0.76604 0.75471 0.74314 0.73135 0.83910 0.86929 0.90040 0.93252* 1.19175 1.15037 1.11061 1.07237 1.30541 1.32501 1.34563 1.36733 .55572 .52425 .49448 .46628 50 49 48 47 44 45 0.69466 0.70711 0.71934 0.70711 0.96569 1.00000 1.03553 1.00000 1.39016 1.41421 1.43956 1.41421 46 45 Degrees Cosines Sines Cotangents Tangents Cosecants Secants Degrees 74 Transmission Towers Properties of the Circle Circumference of Circle of Diameter 1 = - = 3.14159265 Circumference of Circle = 2 * r Diameter of Circle = Circumference X 0.31831 Diameter of Circle of equal periphery as square = side X 1.27324 Side of Square of equal periphery as circle = diameter X 0.78540 Diameter of Circle circumscribed about square = side X 1.41421 Side of Square inscribed in circle = diameter X 0.70711 Arc a = TSTT = 0.017453 r A loU 4b 2 + c 2 4 2 Radius r = T-T Diameter, d , 80 40 Chord, c = 2V 2br b 2 = 2 r sin y Rise, b = rY 2 V 4 r 2 c 2 = tan ~- = 2 r sin 2 4 24 4 Rise, 6 = r '+ y V r 2 ^c 2 . ^ = r + V^ 2 ^ 2 ^ = V r 2 (r + 3; 0) 2 TT = 3. 14159265, log = 0.4971499 ^ = 0.3183099, log =7.5028501 7T 2 = 9.8696044, log = 0.9942997 ^ = 0.1013212, log =7.0057003 = 1.7724539, log = 0.2485749 = 0.5641896, log =7.7514251 = 0.0174533, log = 2.2418774 loU 1 80 = 57.2957795, log = 1.7581226 Transmission Towers 75 Pyramid and Cone Volume of any Pyramid or Cone whether regular or irregular equals product of area of base by one-third perpendicular height, or V = iBh in which V = Volume B = Area of Base h = Perpendicular height Volume of Frustrum of any Pyramid or Cone with parallel ends equals sum of areas of base and top plus square root of their products, all multiplied by one-third the perpendicular height or distance between the two parallel ends, or V = i h (B + \/Bb + b) in which V = volume h = perpendicular distance between parallel ends B = area of base b == area of top 76 Transmission Towers c? Ellipse Area = * ab Center of Gravity of part mnc is at point G cG l = ! a 3 = 0.4244 a = abt. H a cG n = G'G = ! b - = 0.4244 b = abt. Parabola 4 Area = | sh \jh Center of Gravity at point G Hft|bd L-Wi tt_. Semi-Parabola abd or cbd Center of Gravity at Point G 1 dG =|h GG 1 =|-W For the area included between the semi-para- bola abd and its enclosing rectangle aebd, or between the semi-parabola cbd and its en- closing rectangle cfbd, the center of gravity is at the point m. km= w 4 Circular Quadrant Center of Gravity at point G V~2 CG = iRad. X Rad. 0.6002 i CX = XG = J Rad. X = Rad X 0.4244 or abt. Rad. X Transmission Towers 77 Fig. B Towers for Double Circuit 130,000 Volt Line 78 Transmission Towers Fig. C Method of Erecting Towers from Prone Position Transmission Towers 79 Fig. D Method of Erecting Flexible A Frames from Prone Position 80 Transmission Towers I A Fig. E Method of Erecting Towers in Position Transmission Towers 81 Fiji. F Double Circuit Towers, for 66,000 Volt Line 82 Transmission Towers ft Fig. G Special Strain Tower, for Double Circuit 110,000 Volt Line Transmission Towers 83 Fig. H Transposition Tower, for Double Circuit 130,000 Volt Line 84 Transmission Towers Fig. I Railroad Crossing Poles, for 6,600 Volt Line Transmission Towers 85 Fig. J Flexible A Frame, for Double Circuit 66,000 Volt Line 86 Transmission Towers Fig. K Flexible A Frame, for Single Circuit 66,000 Volt Line Transmission Towers 87 L Poles, for Double Circuit 6,600 Volt Line INDEX Anchor Towers Anchorage Designs 50, 51 Angle Towers 45 B Bolt Values. . 44 Catenary 16 Comparison of Parabola and . . Diagram 15 Elastic 19 Circle, Properties of Conductors, Spacing of Cone, Volume of 75 Dead End Towers. . 49 Ellipse ' 76 Erection 55,78,79,80 F Factor of Safety 42 Flexible A Frames, Illustration . 85, 86 Use of.. . 4 Galvanizing 41, 70-71 I Ice and Wind Loads, Standard Practice for 14 L Loads, Kinds of 5-6 Specific 45 Standard Practice for Wind and Ice 14 P Parabola 76 Comparison of Catenary and .... 25 Diagram 20,22,23,27,30 Parabolic Arc 23 Semi 76 Poles, Illustration 84, 87 Railroad Crossing, Illustration ... 84 Use of. 4 Pressure and Wind Velocity, Rela- tion between 12, 13 Pyramid, Volume of 75 Quadrant, Circular 76 S Sag Calculations, Thomas' 33 Curves for 34-35 Relation Between Stress, Tem- perature and 31 Tables.. . 66-69 S Spacing 56 Spans, Reactions for, on Inclines. . . 27 Stringing Wires in, on Steep Grades 29 Specifications for Designs 42 Stress Calculations, Thomas' Curves for 34-35 Relation Between Temperature, Sag and 31 Unit.. . 43 Temperature, Relation Between Stress, Sag and 31 Towers, Anchor 48 Anchorage Designs 50 Angle 45 Dead End 49 Erection 55, 78, 79, 80 Factor of Safety 42 Installations 2, 77-87 Permanent 41 Regular Line 48 Rigid, Use of Spacing of 37, 56 Special 46 Specifications for Designs 42 Standard 48 Strain, Illustration of 82 Temporary 41 Thickness of Materials for 41 Transposition, Illustration of. ... 83 Trigonometrical Formulae 72 Functions 73 U Useful Data. 72-76 W Wind and Ice Loads, Standard Practice for 14 Pressure on Plane Surfaces 7 On Wires . 8 Velocities, Comparison of Indi- cated and Actual 11 Velocity and Pressure, Relation Between 12, 13 Wires, Curves Assumed by 15 Loadings Recommended for 59 Materials, Properties of 59-65 Stringing, in Spans on Steep Grades 29 Tension in, Diagram of Com- ponents of 47 Values Used for Plotting Curves for 36 Wind Pressures on 8 89 Memoranda Memoranda Memoranda Memoranda Memoranda Memoranda PRODUCTS OF THE BLAW-KNOX COMPANY FABRICATED STEEL Fabricated steel, one of the principal products of Blaw-Knox Company, includes mill buildings, manufacturing plants, bridges, crane runways, trusses and other con- struction of a highly fabricated nature. A corps of highly trained engineers is maintained for consulting and designing services. TRANSMISSION TOWERS Four legged straight line or suspension towers, anchor and dead end towers, latticed and channel A-frames, river crossing towers, outdoor sub-stations, switching stations, signal towers, steel poles, derrick towers. We specialize in the design and fabrication of high tension transmission lines. PLATE WORK Riveted, pressed and welded steel plate products of every description, including: accumulators, agitators, water boshes, annealing boxes, containers, digesters, filters, flumes, gear guards, kettles, ladles, pans, penstocks, air receivers, stacks, standpipes, miscellaneous tanks, miscellaneous blast furnace work, etc. BLAW BUCKETS Clamshell buckets and automatic cableway plants for digging and rehandling earth, sand, gravel, coal, ore, limestone, tin scrap, slag, cinders, fertilizers, rock products, etc. For installation on derricks, overhead and locomotive cranes, monorails, dredges, steam shovels, ditchers, cableways, ships for handling cargo and coal, etc. BLAWFORMS Steel forms for every type of concrete construction: aqueducts, bridges, cisterns, columns, culverts, curbs and gutters, dams, factories, floors, foundations, houses, locks, manholes, piers, pipe, reservoirs, roads, sewers, shafts, sidewalks, subways, tanks, tunnels, viaducts, retaining walls, warehouses, etc. FURNACE APPLIANCES Knox patented water cooled doors, door frames, front and back wall coolers, ports, bulkheads, reversing valves, etc., for Open Hearth. Glass and Copper Regenerative Furnaces; water-cooled standings, boshes and shields for Sheet and Tin Mills. THIS BOOK IS DUE ON THE LAST DATE STAMPED BELOW AN INITIAL FINE OF 25 CENTS WILL BE ASSESSED FOR FAILURE TO RETURN THIS BOOK ON THE DATE DUE. THE PENALTY WILL INCREASE TO SO CENTS ON THE FOURTH DAY AND TO $1.OO ON THE SEVENTH DAY OVERDUE. MAR 2 1946 LD 21-100/n-7,'40(6936s) UNIVERSITY OF CALIFORNIA LIBRARY